8.4.2.2. Capacitor charging malfunction (Fault with outdoor unit) (AP1 below refers to the outdoor control panel)
Main detection point:
Use AC voltmeter to check if the voltage between terminal L and N on the wiring board is within 210VAC ~ 240VAC.
If the reactor (L) is correctly connected? If the connection is loose or fallen? If the reactor (L) is damaged?
Fault diagnosis proess:
8.4.2.3 IPM Protection, desynchronizing malfunction, Compressor Phase Overcurrent (AP1 below refers to the
outdoor control panel)
Main detection point:
If the connection between control panel AP1 and compressor COMP is secure? If loose? If the connections are correct?
If the voltage input of the machine is within normal range? (use AC voltmeter to measure the voltage between terminal L
and N on the wiring board XT)
If the compressor coil resistance is normal? If the insulation of compressor coil’s against the copper tube is in good
condition?
Switch on the unit and wait
1 minute.
Use DC voltmeter to
measure the voltage on the
two ends of electrolytic
capacitor.
Voltage higher than 200V Faulty with the voltage testing
circuit on control panel AP1
Replace the control
panel AP1
Measure the AC voltage
between terminal L and N on
wiring board XT(power supply)
Voltage within 210 ~ 250VAC.
Switch off the power and repair
the supply power to restore the
voltage to 210VAC ~ 250 VAC
Re-energize and
switch on the unit
If the fault is
elmininated?
Switch off the power and
wait 20 minutes; or use DC
voltmeter to measure the
voltage on the two ends of
capacitor (test3), until the
voltage is lower than 20V.
Check the connection of
reactor (L in the Electrical
Wiring Diagram)
If the wiring of reactor L is
normal?
Connect the reactor L according
to Electrical Wiring Diagram
Re-energize and
switch on the unit
If the fault is
eliminated
Replace the control panel AP1
End
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No